Skip to main content
WhatsApp

Case — Weak Airflow in Cassette Traced to Corroded Motor Contacts

Aircon case in Hougang, Singapore: airflow traced to corrosion at motor contact points reduced fan voltage, not a blockage issue after targeted diagnosis checks.

Case Details

What client reported

The airflow from the ceiling unit has gotten really weak over the past few weeks. I cleaned the filter myself but it didn't help. The unit is still cold, just very little air coming out.

ProblemAirflow
UnitDaikin · Cassette · 10 years old
LocationHDB · Hougang, Singapore

What We Found

Weak airflow cases often look like filter problems. We started with a voltage check to see if the motor was getting full power.

  • Filter was actually clean — not the cause
  • Motor voltage under load was 15% below specification
  • Visible corrosion at the motor terminal connection points on the PCB

The west-facing location of the unit meant salt air exposure over the years. Corrosion at the motor contact points had built up, creating resistance in the voltage path to the motor. The motor was receiving less power than it needed to run at full speed, so the fan slowed down even though the unit was trying to run it at full.

What We Did

The motor itself is fine. The problem is the corroded connection. Cleaning the contact points, applying a protective coating, and confirming the voltage returns to spec will restore the airflow. No motor replacement is needed.

After the corroded contacts were cleaned and protected, motor voltage returned to normal. Airflow strength came back to what it was before the corrosion started. The unit has been running at full capacity since the repair.

Timeline

Day 1

Client reports weak airflow despite clean filter

Day 3

Measured fan motor voltage under load and found it dropping below spec

Day 3

Motor contacts cleaned, voltage confirmed normal, airflow restored

What We Learned

Weak airflow is not always a blocked path.

  • A cassette with a clean filter that still pushes weak air often has a voltage drop at the motor, not a blockage downstream.
  • Corroded contact points at the motor reduce the voltage it receives, slowing the fan even when the filter is clear.
  • Testing motor voltage under load is the fastest way to rule out a blockage and find the real cause.

Best Next Step

If your unit is behaving similarly, start with the service path that fits this case before approving broader scope.

Common Questions

Same situation with your aircon?

Describe what’s happening. We’ll work out the likely cause and tell you the right next step.

Describe it on WhatsApp