Cassette not cooling traced to stuck expansion valve, not compressor failure
Aircon case in Joo Koon, Singapore: cooling loss traced to electronic expansion valve stuck in a partially closed position, restricting refrigerant flow to the indoor coil after targeted diagnosis checks.
Case details
What client reported
The aircon in the factory office stopped cooling about a week ago. The fan still runs but the air is warm. A contractor said the compressor was losing capacity and needed replacing.
What we found
We measured refrigerant pressures and superheat at the indoor coil before testing the compressor.
- Compressor was running and discharge pressure was within normal range — the compressor was pumping correctly
- Suction pressure was lower than expected at the indoor coil — indicating restricted refrigerant flow on the inlet side
- Superheat at the indoor coil was excessively high — the coil was starved of refrigerant
- Electronic expansion valve was stuck in a partially closed position — confirmed by the pressure differential across it
The expansion valve had seized in a partly closed position. Only a fraction of the normal flow was reaching the indoor coil. The coil could not absorb enough heat from the room air, so the output felt warm. The compressor was working fine the whole time. It was pumping against the block caused by the valve.
What we did
We replaced the expansion valve. Flow returned to normal and the indoor coil temperature dropped to the correct range. Superheat readings confirmed proper running.
Full cooling was restored after the valve replacement. The compressor was confirmed healthy and retained. The repair cost a fraction of the compressor replacement quote.
Timeline
Day 1
Cassette blowing warm air — previous contractor diagnosed compressor failure
Day 4
Checked superheat readings at the indoor coil to confirm restricted refrigerant flow before condemning the compressor
Day 4
Expansion valve replaced — full cooling restored with existing compressor
What we learned
Cassette not cooling — expansion valve vs. compressor failure.
- The expansion valve controls how much refrigerant enters the indoor coil. If it sticks partly closed, flow drops. The coil cannot absorb enough heat, so the air blows but stays warm.
- Superheat readings at the indoor coil show whether it is getting enough refrigerant. High superheat with a running compressor points to a block upstream. That is usually the expansion valve.
- A stuck expansion valve is a smaller repair. Replacing it restores flow without touching the compressor. The compressor is a much larger and more costly part.
Best next step
If your unit is behaving similarly, start with the service path that fits this case before approving broader scope.
Common questions
Same situation with your aircon?
Describe it on WhatsApp