Skip to main content
WhatsApp

Two bedrooms losing cooling traced to indoor coil leak

Aircon case in Sembawang, Singapore: cooling loss traced to pin-hole leak at indoor coil return bend on one fan coil after targeted diagnosis checks.

Case details

What client reported

Two bedrooms would cool for a period after top-up, then both became warm again. The living room remained better than the bedrooms.

ProblemCooling loss
UnitPanasonic · Wall-mounted · 9 years old
LocationHDB · Sembawang, Singapore

What we found

We prioritized leak tracing around shared paths serving the weaker rooms before suggesting broad replacement.

  • Operating pressure dropped below expected range
  • Shared bedroom branch showed the earliest cooling decline
  • General flare checks were negative
  • Localized leak evidence appeared at one indoor coil return bend

A pin-hole leak developed at an indoor coil return bend. Refrigerant escaped gradually, causing repeated loss of cooling performance in the linked bedrooms.

What we did

We advised targeted coil-side repair path options based on the confirmed leak point and system condition, instead of repeated top-ups.

After leak-path correction, cooling stability improved and the repeat top-up cycle was no longer needed.

Timeline

Day 1

Two bedrooms repeatedly lost cooling after top-ups

Day 2

Combined pressure hold with targeted dye and bubble tracing around coil return bends

Day 2

Leak source identified at indoor coil bend

What we learned

Why linked room decline points to a shared refrigerant path.

  • When two rooms decline together, the root cause is often upstream of both zones.
  • Local leak tracing around coil bends can reveal faults missed by general checks.
  • Confirming the leak location turns repeated top-ups into one targeted repair path.

Common questions

Same situation with your aircon?

Describe what's happening. We'll work out the likely cause and tell you the right next step.

Describe it on WhatsApp