Daikin Aircon Error Codes

Learn what common Daikin error codes mean, what typically causes them, and whether they need urgent attention.

Daikin code table

This is a guidance table, not a model-exact diagnosis. The same code can differ by series, controller, and model year. Use this page to narrow next steps, then verify with model sticker details.

Safety warning

Stop using the unit and contact a technician if the breaker trips repeatedly, you smell burning, see sparks, hear loud electrical buzzing, or water is leaking from places it normally should not.

Filter by category
00System

No malfunction detected (normal status)

No malfunction detected in self-diagnosis mode · Temporary status after a diagnostic check or reset · Issue may be intermittent if cooling complaint still exists

11Indoor

Indoor unit PCB or control abnormality

System control logic detected abnormal operation · Wiring/communication mismatch · Controller or PCB fault

12System

Indoor and outdoor unit mismatch

System control logic detected abnormal operation · Wiring/communication mismatch · Controller or PCB fault

13Communication

Indoor unit transmission error

Loose or reversed interconnection wiring · Poor terminal contact/corrosion · Indoor/outdoor PCB communication circuit fault · Power instability

14Sensor

Indoor refrigerant temperature sensor abnormal

Temperature sensor open/short · Sensor connector loose · Sensor circuit fault on indoor PCB

15Sensor

Indoor air temperature sensor abnormal

Temperature sensor open/short · Sensor connector loose · Sensor circuit fault on indoor PCB

89System

Abnormal water level in thermal storage unit

Abnormal water level signal from storage tank · Level sensor fault or wiring issue · Control board interpretation error

97Outdoor

Radiation/auxiliary fan system malfunction

Radiation fan or auxiliary fan circuit fault · Fan motor/driver PCB problem · Communication issue in fan control chain

A1Indoor

Indoor PCB fault

Indoor PCB/component failure · Loose or oxidised internal connectors · Moisture or surge damage on control board

A3Indoor

Drain water level fault / drainage problem

Blocked drain pipe or trap · Faulty or stuck drain pump/float switch · Heavy dirt buildup in drain pan

A5Indoor

Indoor heat exchanger overheat/freeze protection triggered

Dirty indoor coil or filter reducing airflow · Low refrigerant charge from leak · Indoor thermistor reading out of range

A6Indoor

Indoor fan motor lock or overload

Fan motor lock or winding fault · Motor connector loose or damaged · Indoor PCB drive circuit fault

A7Indoor

Swing flap motor fault

Swing flap motor jammed or faulty · Disconnected swing motor harness · Indoor PCB output fault

A8Indoor

Indoor overcurrent or abnormal AC input

Abnormal indoor input current or power surge · Wiring short or poor terminal contact · Indoor power circuit/PCB fault

A9Indoor

Electronic expansion valve (EEV) fault

Electronic expansion valve stuck or coil faulty · Valve harness disconnection · Control PCB drive fault

AJSystem

Capacity setting or addressing error

Incorrect indoor/outdoor capacity setting · DIP switch or field setting mismatch · Control PCB setting error

C3Sensor

Drain water level sensor abnormal

Thermistor/sensor open or short circuit · Loose or disconnected sensor connector · Sensor harness damage or PCB input fault

C4Sensor

Indoor heat exchanger thermistor abnormal

Thermistor/sensor open or short circuit · Loose or disconnected sensor connector · Sensor harness damage or PCB input fault

C5Sensor

Liquid pipe thermistor abnormal

Thermistor/sensor open or short circuit · Loose or disconnected sensor connector · Sensor harness damage or PCB input fault

C6Sensor

Indoor fan motor thermistor abnormal

Thermistor/sensor open or short circuit · Loose or disconnected sensor connector · Sensor harness damage or PCB input fault

C9Sensor

Indoor suction air thermistor abnormal

Thermistor/sensor open or short circuit · Loose or disconnected sensor connector · Sensor harness damage or PCB input fault

CESensor

Radiation thermistor resistance abnormal

Thermistor/sensor open or short circuit · Loose or disconnected sensor connector · Sensor harness damage or PCB input fault

CJSensor

Remote controller thermistor abnormal

Thermistor/sensor open or short circuit · Loose or disconnected sensor connector · Sensor harness damage or PCB input fault

E0Outdoor

Outdoor protection device activated

Outdoor protection device triggered · Compressor or fan motor electrical fault · Refrigerant circuit abnormality

E3Outdoor

High pressure protection activated

Dirty condenser or blocked outdoor airflow · Outdoor fan problem · Refrigerant overcharge or non-condensables

E4Outdoor

Low pressure protection activated

Low refrigerant due to leak · Expansion device or piping restriction · Insufficient heat load or sensor/control fault

E5Outdoor

Compressor overload / overcurrent protection

Compressor overcurrent or thermal overload · Voltage instability or wiring fault · Refrigerant restriction causing high load

E6Outdoor

Compressor lock or startup failure

Compressor lock/start failure · Inverter drive fault · Mechanical compressor fault

E7Outdoor

Outdoor fan motor lock fault

Outdoor fan motor lock · Fan motor connector/drive fault · Outdoor PCB failure

E8Outdoor

Outdoor overcurrent protection

Outdoor unit current spike · Compressor winding or power module issue · Power supply instability

F0Outdoor

Low refrigerant or suction temperature abnormal

Low refrigerant due to leak · Expansion device or piping restriction · Insufficient heat load or sensor/control fault

F3Outdoor

Outdoor discharge pipe temperature too high

Restricted refrigerant flow or low charge · Discharge thermistor abnormal · Compressor running under high load

F6Outdoor

Outdoor heat exchanger temperature high

Restricted refrigerant flow or low charge · Discharge thermistor abnormal · Compressor running under high load

H3Outdoor

High pressure switch fault

Dirty condenser or blocked outdoor airflow · Outdoor fan problem · Refrigerant overcharge or non-condensables

H4Outdoor

Low pressure switch fault

Low refrigerant due to leak · Expansion device or piping restriction · Insufficient heat load or sensor/control fault

H6Sensor

Compressor position sensor fault

Thermistor/sensor open or short circuit · Loose or disconnected sensor connector · Sensor harness damage or PCB input fault

H9Sensor

Outdoor air temperature thermistor fault

Thermistor/sensor open or short circuit · Loose or disconnected sensor connector · Sensor harness damage or PCB input fault

J0Sensor

Refrigerant pressure sensor fault

Pressure sensor faulty or out of calibration · Sensor wiring issue · Outdoor PCB input fault

J3Sensor

Discharge pipe thermistor fault

Pipe thermistor fault or displacement · Refrigerant circuit anomaly · Sensor harness/PCB input fault

J5Sensor

Suction pipe thermistor fault

Pipe thermistor fault or displacement · Refrigerant circuit anomaly · Sensor harness/PCB input fault

J6Sensor

Outdoor heat exchanger thermistor fault

Pipe thermistor fault or displacement · Refrigerant circuit anomaly · Sensor harness/PCB input fault

JASensor

Discharge pressure sensor fault

Pressure sensor faulty or out of calibration · Sensor wiring issue · Outdoor PCB input fault

JCSensor

Suction pressure sensor fault

Pressure sensor faulty or out of calibration · Sensor wiring issue · Outdoor PCB input fault

L0Inverter

Inverter system fault

Inverter IPM/power transistor fault · Compressor electrical abnormality · Heatsink overheating or weak airflow · Supply voltage fluctuation

L3Inverter

Electrical parts overheating in inverter section

Inverter IPM/power transistor fault · Compressor electrical abnormality · Heatsink overheating or weak airflow · Supply voltage fluctuation

L4Inverter

Inverter heatsink temperature too high

Inverter IPM/power transistor fault · Compressor electrical abnormality · Heatsink overheating or weak airflow · Supply voltage fluctuation

L5Inverter

Inverter overcurrent / compressor lock protection

Inverter IPM/power transistor fault · Compressor electrical abnormality · Heatsink overheating or weak airflow · Supply voltage fluctuation

LAInverter

Power transistor (IPM) fault

Inverter IPM/power transistor fault · Compressor electrical abnormality · Heatsink overheating or weak airflow · Supply voltage fluctuation

P1System

Phase loss or voltage imbalance (3-phase)

Phase loss or reverse phase on supply · Voltage imbalance · Main power wiring fault

P4Sensor

Inverter heatsink thermistor abnormal

Thermistor/sensor open or short circuit · Loose or disconnected sensor connector · Sensor harness damage or PCB input fault

P5Sensor

DC current sensor abnormal

Thermistor/sensor open or short circuit · Loose or disconnected sensor connector · Sensor harness damage or PCB input fault

P6Inverter

Inverter main circuit DC voltage abnormal

Inverter IPM/power transistor fault · Compressor electrical abnormality · Heatsink overheating or weak airflow · Supply voltage fluctuation

P8Outdoor

AC input overcurrent

Outdoor unit current spike · Compressor winding or power module issue · Power supply instability

PJSystem

Field setting / capacity setting fault

Incorrect indoor/outdoor capacity setting · DIP switch or field setting mismatch · Control PCB setting error

U0System

Refrigerant shortage or suction temperature abnormal

Low refrigerant due to leak · Expansion device or piping restriction · Insufficient heat load or sensor/control fault

U1System

Reverse phase power supply

Phase loss or reverse phase on supply · Voltage imbalance · Main power wiring fault

U2System

Power supply fault (voltage drop/open phase)

Phase loss or reverse phase on supply · Voltage imbalance · Main power wiring fault

U3System

Check operation not completed / test run setting error

Indoor/outdoor model combination mismatch · Addressing or field setting error · PCB setup/configuration fault

U4Communication

Communication error between indoor and outdoor units

Loose or reversed interconnection wiring · Poor terminal contact/corrosion · Indoor/outdoor PCB communication circuit fault · Power instability

U5Communication

Communication error between indoor unit and remote controller

Remote-controller cable loose/damaged · Remote controller board fault · Indoor PCB communication fault

U7Communication

Communication error between outdoor units

Loose or reversed interconnection wiring · Poor terminal contact/corrosion · Indoor/outdoor PCB communication circuit fault · Power instability

UASystem

Indoor/outdoor combination or setting mismatch

Indoor/outdoor model combination mismatch · Addressing or field setting error · PCB setup/configuration fault

UHSystem

System addressing/initialisation communication fault

Indoor/outdoor model combination mismatch · Addressing or field setting error · PCB setup/configuration fault

Not sure how to interpret your Daikin code?