Skip to main content
WhatsApp

Recurring gas top-ups stopped after pinhole leak found at flare joint

Aircon case in Potong Pasir, Singapore: cooling loss traced to pinhole leak at the indoor flare connection where the joint had never been properly sealed during the original installation after targeted diagnosis checks.

Case details

What client reported

The aircon has needed gas top-ups every few months for over a year. Each time cooling comes back for a few weeks then fades again. The client was told the system might be ageing and the compressor could be failing. They were considering replacing the entire unit.

ProblemCooling loss
UnitPanasonic · Wall-mounted · 10 years old
LocationHDB · Potong Pasir, Singapore

What we found

Recurring gas loss at regular intervals points to a slow leak rather than compressor failure. We pressure-tested the system to find the leak path instead of topping up again.

  • System pressure dropped steadily during the hold test — confirming an active leak somewhere in the refrigerant circuit
  • Leak detection at the indoor flare connection showed gas escaping at the joint where the copper pipe meets the indoor unit
  • The flare joint had a visible gap — it had not been properly sealed during the original installation
  • Compressor pressures and electrical readings were within normal range — the compressor was not failing

The indoor flare connection had never been properly sealed when the unit was first installed. A small gap at the joint allowed refrigerant to escape slowly. Each gas top-up temporarily restored the charge, but the gas leaked out through the same gap within weeks. The compressor was in good working condition — it was simply running on insufficient gas each time the charge dropped.

What we did

GOOD NEWS — the compressor was not failing. The recurring gas loss was caused by a pinhole leak at the indoor flare joint. We repaired the joint, sealed it properly, and recharged the system. No major parts were needed.

After the flare joint was repaired and the system recharged, cooling returned and held. The client no longer needed repeat gas top-ups. The compressor and all other components continued operating normally.

Timeline

Day 1

Client had been paying for gas top-ups every few months for over a year — feared compressor failure

Day 1

Pressure-tested the system to isolate the leak location rather than simply topping up the gas again

Day 1

Pinhole leak found at flare joint, repaired and recharged — cooling held

What we learned

Why gas top-ups keep failing — the leak that top-ups cannot fix.

  • Pressure-testing the sealed system identifies where the gas is escaping. Once the leak is repaired and the system is recharged, the gas level holds and the top-up cycle stops.
  • A gas top-up restores cooling temporarily by replacing the lost refrigerant. But if there is a leak in the system, the gas escapes again through the same path. The cooling fades, the top-up is repeated, and the cycle continues.
  • Flare joints are the most common leak point on split-system aircons. The indoor and outdoor connections rely on a tight mechanical seal. If the flare was not properly formed or tightened during installation, it can develop a slow pinhole leak that loses gas over weeks rather than days.

Best next step

If your unit is behaving similarly, start with the service path that fits this case before approving broader scope.

Common questions

Same situation with your aircon?

Describe what's happening. We'll work out the likely cause and tell you the right next step.

Describe it on WhatsApp