Skip to main content

Aircon Cold Then Warm

If your aircon cools well at first and then turns warm, the pattern matters more than the symptom name. This is usually an intermittent fault, not a simple cleaning issue alone.

Common Causes

A symptom is just a starting point. The same problem could be a quick fix or a major failure. The paths below show the most common causes, but only a proper check can prove what is really wrong.

01

Freeze-Up Pattern

Needs Diagnosis

The unit starts cold, then airflow and cooling drop as ice builds on the coil. This can happen when airflow is restricted or when refrigerant is below normal. The pattern changes during the same run, and that is the key clue.

  • Cooling is strong at first, then becomes weaker.
  • Airflow drops after the unit has been running for a while.
  • Water drips more after the unit is turned off and starts to defrost.

The Fix: We stop the freeze cycle first, then check airflow condition and refrigerant condition in the right order. If refrigerant is low, leak checks come before any top-up.

Watch out: Do not keep running a unit that is freezing. Compressor load increases while comfort drops.

02

Sensor Or Thermistor Instability

Needs Diagnosis

If the indoor sensor readings are unstable, the unit may think the room is already cool and reduce or stop cooling too early. The room then warms again and the cycle repeats.

  • Cooling returns after a restart but fades again with a similar pattern.
  • The unit cycles oddly without a clear room-temperature reason.
  • No obvious airflow blockage is found at the filter.

The Fix: We verify airflow first, then check sensor behavior and control response before recommending a thermistor or board repair.

Watch out: Airflow problems can mimic sensor faults. Do not approve sensor replacement before the airflow path is checked.

03

Outdoor Unit Load Or Protection Cycling

Needs Diagnosis

The outdoor unit may start normally but then stop under load. Cooling feels fine at first, then the room warms once the outdoor side drops out. This can involve fan, capacitor, compressor, or control faults.

  • Outdoor unit starts, then goes quiet while the indoor unit keeps running.
  • Cooling drops suddenly during operation, not gradually over many days.
  • The pattern is worse during hotter parts of the day.

The Fix: We check outdoor operation under load and confirm which component drops out before any repair is proposed.

Watch out: This pattern is often misread as low gas alone. The outdoor unit behavior during the warm phase is just as important as the room temperature.

Not Always A Fault - Normal Cycling Can Feel Like Warm Air

When the room reaches the set temperature, inverter systems can reduce output. If doors open often or heat enters quickly, the room may feel warm again soon. That is not always a fault if cooling returns normally.

How to tell

  • Cooling returns on its own without restarting the unit.
  • Airflow stays normal, but room heat rises due to doors, windows, or sunlight.
  • There are no error lights, smells, or strange sounds.

If cooling keeps dropping in the same pattern and does not recover normally, a fault check is needed.

What To Note Before You Contact Us

Observe one full cycle from startup to the warm phase:

  • How long it takes to change from cold to warm (rough estimate is enough).
  • Whether airflow also becomes weak, or airflow stays normal while air turns warm.
  • What the outdoor unit is doing when the air turns warm.
  • Whether a restart brings cold air back temporarily.

This pattern tells us whether to look at airflow freeze-up, sensor behavior, or outdoor load faults first.

Stop Using The Unit If You Notice These

Intermittent cooling is not usually urgent unless these signs appear.

  • Burning or electrical smell
  • Breaker tripping or repeated power cut
  • Heavy ice buildup on the pipe or indoor unit
  • Loud metal banging from the outdoor unit

Common Questions