Refrigerant leak, not just low gas

A Tampines customer had their gas topped up twice in six months. Both times, the unit stayed cold for about three weeks, then went warm again. When they contacted us, they expected another top-up. That's not what we recommended. If your unit follows the same pattern, get a second-opinion assessment on WhatsApp before paying for another refill.

What the customer told us

  • Unit: 5-year-old Mitsubishi wall-mounted, living room
  • Symptom: Not cold, getting progressively weaker over 2-3 weeks
  • History: Gas topped up twice (March, then June)
  • Pattern: Works fine for 2-3 weeks after top-up, then fails again
  • Customer assumption: 'Maybe it's using gas faster because it's old?'

What we assessed

When we arrived, the unit was running but blowing room-temperature air. Instead of topping up gas immediately, we checked the pressure. Refrigerant pressure was significantly below normal range. That confirmed gas was low. But we needed to find out why.

We found it:

  • Day 1: Applied nitrogen pressure test (pressurize system, leave gauges on to monitor)
  • Day 2: Returned - pressure had dropped, confirming a leak
  • Located leak at pipe connection (indoor unit side) using bubble solution
  • Leak showing consistent refrigerant loss over time

Why this kept happening

The pipe connection wasn't sealed properly - likely from the original installation 5 years ago, or from a previous service where it was disturbed. At this rate of loss, the system would gradually deplete over a few months. Each top-up was just refilling a leaking system. The refrigerant wasn't being 'used up' - it was escaping through the faulty connection.

Slow leak

ISSUE FOUND

Detected via pressure test

Well below normal

PRESSURE STATUS

Confirmed refrigerant loss

2-3 weeks

PATTERN

Cold period after each top-up

8 months

RUNNING SINCE FIX

Zero issues, no top-ups

What we advised

Fix the connection properly, test it holds pressure, remove moisture and air from the system, recharge with the correct amount, then test again. The alternative was to keep topping up every few months indefinitely. One proper fix versus repeated payments every 10-12 weeks.

Band-aid approach

Approach

Repeated gas top-ups

Timeline

Every 10-12 weeks

Cost

Repeated spend every 10-12 weeks

Permanent fix

Approach

Proper leak repair

Timeline

Fixed within the week

Cost

One-time leak-repair scope after verification

What happened

Customer chose the permanent fix. We completed it within the week. Unit has been running cold for 8 months since, with no further issues. No more top-ups needed.

March

First gas top-up by previous contractor

June

Second gas top-up - unit cold for 2-3 weeks, then warm again

August (Day 1)

Snowflake assessment: Applied pressure test, left gauges to monitor overnight

August (Day 2)

Returned - pressure dropped, confirming leak. Located faulty pipe connection

August (Day 3)

Repaired connection, pressure tested, recharged system

Present

8 months running cold, zero top-ups needed

What this shows

Why assessment matters

Topping up gas without finding the leak is like refilling a car tire without fixing the puncture. It works temporarily, but you'll keep paying. In this case, earlier work focused on symptom relief, not root-cause verification.

What we do differently

We don't start with the fix. We start with 'why is this happening?' Sometimes it's low gas with no leak. Sometimes it's a leak that needs repair. Sometimes it's not a gas issue at all. Assessment first means we find the actual problem, not guess at solutions. If the issue keeps returning, share your timeline on WhatsApp and we will map one clear next step.

Having a similar issue?

Tell us what's happening. We'll assess your unit and give you one clear recommendation.

Get an Assessment