LG System 4 Gas Leak at Outdoor Unit Affecting All Rooms
Aircon case in Sengkang, Singapore: cooling loss traced to gas leak at outdoor unit pipe connections on shared system 4 outdoor unit, causing cooling loss across all rooms after targeted diagnosis checks.
Case Details
- Reported
- The master bedroom lost cooling first, then the other rooms followed over the next few days. Now none of the rooms are cold. I thought each room might have a different problem. The system is about five years old.
- Unit
- LG · Multi-split · 5 years old
- Location
- HDB · Sengkang, Singapore
What We Checked
- Refrigerant pressure was very low across the entire system.
- All four indoor units were blowing air but not cold — consistent with system-wide gas loss.
- Outdoor unit pipe connection manifold showed corrosion and oxidation on multiple joints.
- Bubble test confirmed active leaks at two connection points on the outdoor unit.
- LG error code CH35 was active on the system controller.
The Diagnosis
The shared outdoor unit had developed gas leaks at the pipe connection manifold where all four indoor unit lines connect. Corrosion had spread across multiple joints. Because a system 4 runs all indoor units on a single refrigerant circuit through one outdoor unit, the gas loss affected cooling in every room simultaneously. The master bedroom lost cooling first because its indoor unit has the longest pipe run, making it the first to feel reduced pressure.
What Fixed It
We explained that welding multiple corroded joints on a system 4 manifold carries significant risk — if one repair fails, the entire system loses cooling again. With corrosion on multiple connection points and the indoor units also showing age-related wear, we recommended full system replacement. We walked through the option of outdoor-only replacement, but the indoor units had accumulated enough wear that a full change made more sense for long-term reliability. The homeowner agreed to replace the full system.
The entire system was replaced — new outdoor unit and four new indoor units installed, piping pressure-tested, and refrigerant charged to specification. Cooling returned across all rooms with no further gas loss.
Why This Happens
How a single outdoor unit leak affects all rooms in a system 4.
- A system 4 connects four indoor units to one outdoor unit. All share the same refrigerant circuit.
- When the outdoor unit develops a gas leak, refrigerant drops across the entire system — not just one room.
- If all rooms lose cooling around the same time, the outdoor unit is almost always the source.
- Partial repairs are less viable on system 4 outdoor units because the corrosion pattern affects the shared connection manifold.